6 Load, 1000 Amps Per Load
| CURRENT | ||
| Maximum Load | 6000A | |
| Per Load | 1000A | |
| Load Complement | 2,4 or 6 | |
| DISTRIBUTION OUTPUT SELECTION | ||
| Type | Size | Positions |
| TLS | 1-125A | 1 |
| TPW | 150-250A | 2 |
| TPC | 3-125A | 1 |
| Elec. Trip Breakers | 2-100 | 1 |
| Elec. Trip Breakers | 125-150 | 2 |
| Elec. Trip Breakers | 200-250 | 3 |
| DOCUMENTATION | ||
| Product Manual | 4385069P-1PD | |
| J Drawing | J4385069P-1 | |
| MECHANICAL | ||
| Dimensions | 84"H x 15"D x 26"W | |
| Weight | 444 lbs. | |
| Battery Return | External Only | |
| ENVIRONMENTAL | ||
| Heat Output | 2738 BTU/hr | |
| Operating Temperature | -5°C to +50°C (+23°F to +122°F) | |
| CABLING | ||
| Input Cable Size | 4 – 750 kcmil maximum per load 4 – 500 kcmil maximum per load 4 – 350 kcmil maximum per load 8 – 4/0 flex maximum per load |
|
| Input Hole Spacing | 3/8" on 1" (4 sets per load) | |
| Output Cable Size | 4/0 maximum (with adapter plates) | |
| Output Lug Size | Type Position | Terminations |
| 1/4" on 5/8" center on terminal block | TLS, TPC, Breakers; 2-100 | 1- Cables 2/0 Standard |
| 1/4" on 5/8" center on termination plate | TPW; 2 & 3 Pole breakers | 1 – 4/0 Flex maximum |
| SAFETY AND COMPLIANCE | ||
| UL Listings | UL60950, UL198L, UL489 | |
| NEBS Certification | Pending | |
| Seismic Rating | Zone 4 | |
| All Ratings are based on a fully equipped, 6 panel BDFB/BDCBB | ||