200 Amps @ -54VDC
| INPUT | |
| Voltage Range | 90 – 275 VAC |
| Frequency | 45 to 66 Hz |
| Current | 8.5A @ 208/240VAC 11.5A @ 120VAC |
| CUSTOMER PROVIDED PROTECTION | |
| List 110 Dual AC Feed | 25A Circuit breakers |
| List 111 Individual AC Feed | 15A Circuit breakers |
| OUTPUT | |
| Voltage Range | -42VDC to -58VDC |
| Current @ 208/240VAC | 1620W (30 Amps) Shelf - rectifier rating x quantity equipped |
| Available Recharge current @ 208/240VAC | 33.8 Amps @ -48VDC |
| Current @ 90VAC | 810W (15 Amps) |
| Current @ 208/240 @ +75°C | 810W (15 Amps) |
| Efficiency | >92% |
| NOISE (PER RECTIFIER) | |
| Voice Band |
≤ 24 dBrnc CCITT, w/ batteries ≤ 40 dBrns CCITT, w/o batteries |
| Wide Band | ≤ 100 mVrms @ 10k to 20M Hz |
| Acoustic | ≤ 55 dB(A) |
| DISTRIBUTION | |
| Option #1 |
Four (4) Plug-in Circuit Breaker Positions, Ten (10) GMT |
| Option #2 | Two (2) Plug-in Circuit Breaker Positions for Distribution loads, Two (2) Plug-in Circuit Breaker Positions for Battery Strings, Ten (10) GMT |
| CB/Fuse Options | Circuit Breakers 1-100A Telpower TLS Fuse 1-125A GMT Fuses up to 20A |
| MECHANICAL | |
| Weight | 14.5 lbs basic shelf 7.9 lbs 19" basic shelf 5.5 lbs rectifier |
| Dimensions |
3.5” H x 12.3” D x 19” or 23” mounting widths |
| Cooling | Vertical fan cooled with speed control |
| QSC1100 CONTROLLER | |
| Display | 128 X 128 LCD |
| Local | Rotary Encoder Knob or PC via RJ45 |
| Programmable Relays | 6 |
| External Alarm Inputs | 4 |
| Controller Security | Administrator optioned front panel security Physical toggle allows for security lockdown |
| ENVIRONMENTAL | |
| Storage Ambient |
-40°F to +185°F (-40°C to +85°C) |
| Operating Ambient | -40°F to +167°F (-40°C to +75°C) Full Power rating to +65°C, linear derating to half power at +75°C |
| Humidity | < 95% non-condensing |
| Heat Dissipation | < 470 BTU/hr per rectifier |
| MTBF | > 435K hours |
| SAFETY AND COMPLIANCE | |
| NEBS GR1089 and GR63 | |
| UL60950 | |
| DOCUMENTATION | |
| Product Manual |
4380434PD |
| J-Specification | J438171 |